| air shower |
 |
The air showers remove surface lint and dust from garments of workers entering the clean room without time consuming and counterproductive decontamination delays.Based on "fail safe" principles, the air shower remove contaminants from workers and air entering the clean room. They prevent accidental contamination due to premature or mistaken opening of the pressure-sealed doors. Contaminated air is returned through a low-wall prefilter for delivery to the HEPA module. Maintenance and filter replacement are simplified and performed primarily from outside to minimize downtime during servicing. |
| Features
 |
Heavy-duty aluminum doors with full glazing, hinge sets and electrical locks for long, trouble free Performance. |
 |
Logic circuitry with built-in wall sensor activates unit. |
 |
HEPA Filter eliminates 99.99% of all particles 0.3 microns or larger. |
 |
Electrical interlock system prevents accidental access to clean room. |
 |
1-180 second adjustable time cycle. |
 |
Blower generates minimum nozzle velocity of6,000 FPM. |
 |
All locks open automatically in the event of power failure. |
 |
1" nozzles effectively "wash" the worker. |
 |
Durable Kydex® laminated interior. |
 |
Modular construction with complete drawing and installation package; provides flexibility for moving within building and during installation. |
 |
24 VDC passage lock includes built-in microswitch with fail-safe mechanism, as opposed to solenoid plunger which is prone to failure |
 |
Emergency panic buttons with logic circuitry, one inside and one outside each door, will deactivate the system. |
 |
Audible alarm. |
 |
Standard operating voltage (208/220-230 V, 60 Hz, 3 phase) is transformed internally. |
Options
 |
Safety plate glass or amber acrylic panels. |
 |
Electric eye activated |
 |
All stainless steel interior and/or exterior |
 |
99.9995% ULPA filter at 0.12 microns, laser scanned |
 |
460 V 60 Hz 3 phase or 220 V 50 Hz 3 phase operation |
 |
Ceiling mounted HEPA filtration for continuous purge of enclosure |
 |
Sliding doors |
 |
High speed roll up doors |
Specifications
 |
Blower/Motor: 208/220-230 3 phase, 60 Hz to main power supply. High pressure, direct-drive blower with self-cleaning, radial blade paddle wheels to produce 6,000 FPM high-velocity, lowpressure air. Fan cooled motor; drip-prooffor continuous-duty operation. |
 |
Control-Circuitry: 24 VAC and DC by internal transformer. |
 |
Interior Lighting: 110, 120 VAC, single-phase, 60 Hz recessed fluorescent by internal transformer. (Note: All wiring meets National Electrical Code. See General Specifications for other power
options ) |
| Click here for product images |
|
|
|
|
|
|
|